Maytag MDG50PCC Clothes Dryer User Manual


 
10 Maytag Co. 113198-5
NOTE: Ductwork should be laid out in such a manner where allowances are made at rear area of the
dryer for removal of rear service panels or guards.
SINGLE DRYER VENTING
HORIZONTAL VENTING
When a single 8-inch (20.32 cm) horizontal vent is used, the ductwork to the outlet cannot exceed 20 feet
(6.1 meters), refer to
Illus. A below. This calculation of 20 feet (6.1 meters) compensates or allows for the use
of a maximum of only one (1) elbow (which is the outside outlet protection).
Illus. A
IMPORTANT: Exhaust back pressure measured by a manometer at the dryer exhaust duct area must
be no less than 0 and must not exceed 0.3 inches (0.74 mb) of water column (W.C.).
VERTICAL VENTING
When vertical single 10-inch (25.4 cm) venting is used (refer to Illus. B below), the ductwork from the dryer to
the outside outlet
cannot exceed 40 feet (12.19 meters). This calculation compensates for the use of a maximum
of three (3) elbows including the two (2) elbows creating the 180° (turned downward) outside outlet.
Illus. B
JEV 04/12/02