© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Tumblers – 120 and 170
4-08-45
17
Electrical Requirements
Refer to Table 5.
NOTE: Minimum wire sizes are obtained from
Canadian Electrical Code and are intended for use
as a guideline only. Electrical connections should be
made only by a qualified electrical contractor in
accordance with all applicable local and national
requirements.
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.
NOTE: Use copper conductors only.
NOTE: 3 Phase Only– Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of “single
phasing” and causing premature failure of the
motor(s).
For 120 Pound Tumbler Models
Serial Plate Rating
Terminal Block
Connections Required
Rated
Current*
Breaker
Rating
Breaker
Poles
Recommended
Wire Size
208-230V/60Hz/3ph
L1, L2, L3 and ground 7.7 15 Amps 3
14 AWG (2.08 mm
2
)
380-415V/50Hz/3ph
L1, L2, L3 and ground 3.8 10 Amps 3
14 AWG (2.08 mm
2
)
380V/60Hz/3ph
L1, L2, L3 and ground 4.1 10 Amps 3
14 AWG (2.08 mm
2
)
440V/60Hz/3ph
L1, L2, L3 and ground 3.8 10 Amps 3
14 AWG (2.08 mm
2
)
460-480V/60Hz/3ph
L1, L2, L3 and ground 3.9 10 Amps 3
14 AWG (2.08 mm
2
)
* Current ratings vary slightly depending on model; refer to serial plate.
For 170 Pound Tumbler Models
Serial Plate Rating
Terminal Block
Connections Required
Rated
Current*
Breaker
Rating
Breaker
Poles
Recommended
Wire Size
208-230V/60Hz/3ph
L1, L2, L3 and ground 13.5 20 Amps 3
12 AWG (3.31 mm
2
)
380-415V/50Hz/3ph
L1, L2, L3 and ground 6.9 15 Amps 3
14 AWG (2.08 mm
2
)
380V/60Hz/3ph
L1, L2, L3 and ground 6.6 15 Amps 3
14 AWG (2.08 mm
2
)
440V/60Hz/3ph
L1, L2, L3 and ground 6.4 15 Amps 3
14 AWG (2.08 mm
2
)
460-480V/60Hz/3ph
L1, L2, L3 and ground 6.7 15 Amps 3
14 AWG (2.08 mm
2
)
* Current ratings vary slightly depending on model; refer to serial plate.
Table 5