Local Energy Mode
The FPE-1000-CITY connects Local Energy signaling devices to the FPA-1000 fire panel for auxiliary service
operation.
Refer to the FPA-1000 Installation and Operation Guide for a listing of compatible Gamewell devices.
Specifications
Terminal
Figure 4 Local Energy Mode
ALM - | + Connects to Municipal Master Box
SUP - | + Not used
Circuit resistance 65 Ω
Wire gauge
12 to 18 AWG (3.3 mm
2
to 0.8 mm
2
)
Operating temperature 32 °F to 120 °F (0 °C to 49 °C)
Storage temperature -4 °F to 140 °F (-20 °C to 60 °C)
Relative humidity Up to 93%, non-condensing
Reverse Polarity Mode
Nominal Voltage 24 V DC nominal (26.4 V DC maximum), power-limited, supervised
Output current 33 mA maximum
Supervisory/standby current 5 mA
Local Energy Mode
Type of connection In series
Alarm, trip coil 24 V DC
Alarm current 250 mA (momentary, <1 ms)
Supervisory/standby current <50 mA DC
Trip coil resistance 14.5 Ω
Nominal coil voltage 3.65 V DC, power-limited, supervised
ALM-
ALM+
SUP-
SUP+