American Dryer Corp. MLG31PCA Clothes Dryer User Manual


 
20
3.
Grounding
Grounding (earth) connections must be provided and installed in accordance with state and local codes. In
the absence of these codes, grounding must conform to applicable requirements of the National Electrical
Code ANSI/NFPA NO. 70-LATEST EDITION, or in Canada, the installation must conform to applicable
Canada Standards: Canadian Electrical Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION. The
ground connection may be to a proven earth ground at the location service panel.
For added personal safety, when possible, it is suggested that a separate ground wire (sized per local codes)
be connected from the ground connection of the dryer to a grounded cold water pipe. DO NOT ground to
a gas pipe or hot water pipe. The grounded cold water pipe must have metal to metal connections ALL
the way to the electrical ground. If there are any nonmetallic interruptions, such as, a meter, pump, plastic,
rubber, or other insulating connectors, they must be jumped out with No. 4 wire and securely clamped to
bare metal at both ends.
IMPORTANT: For personal safety and proper operation, the dryer must be grounded.
4. Electrical Service Specifications (per pocket)
IMPORTANT: The dryer must be connected to the electrical supply shown on the data label is
located in the gas train area (right inside wall near sail switch) behind the middle
control (access) door.
WARNING: Any damage done to dryer components due to improper voltage application or
connections will automatically VOID THE WARRANTY.
NOTE: Contact factory for electrical information not listed.
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact
voltage.
NOTES: 1. Fuse ratings are dual element time delay current limiting, class RK1 or RK5 ONLY.
2. Circuit breakers are thermal magnetic (industrial) motor curve type ONLY. For others,
calculate/verify correct breaker size according to appliance amp draw and type of breaker
used.
NOTE: Manufacturer reserves the right to make changes in specifications at any time without notice
or obligation.
MLG31PCA
ELECTRICAL SERVICE SPECIFICATIONS (PER POCKET)
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
120 2 6 * 8 15
208 2 4 * 5 15
240 2 4 * 6 15
* AWG Stranded Wire Type ... size wire as per National Electrical Code or local codes.