American Dryer Corp. MDG-50 Clothes Dryer User Manual


 
13
SINGLE DRYER VENTING
IMPORTANT: For exhaust duct runs over 30 feet a minimum size of 10 inches must be used.
HORIZONTAL VENTING
When horizontal single 8-inch venting is used, the duct work to the outlet cannot exceed 30 feet (refer to Illus.
A below). This calculation of 30 feet compensates or allows for the use of a maximum of only one (1) elbow
(which is the outside outlet protection).
Illus. A