2.9.3 Digital Communicator and Annunciators
2.9.3.1 ACM-8RF Relay Control Module
The ACM-8RF module provides eight Form-C relays with contacts rated for 5
amps. When installed with an MS-9200UDLS FACP, the ACM-8RF modules
provide relay activation for each of the 99 possible FACP zones plus special
functions. Options exist to allow for alarm only or alarm and trouble activation per
zone. Output activation for general alarm, general trouble, general supervisory,
NAC fault, AC fail, walktest start and battery trouble are also available. The ACM-
8RF can be mounted remotely in an ABS-8RF annunciator surface-mount backbox.
Refer to the ACM-8RF manual for information on setting module switches for
addressing and relay functions.
2.9.3.2 ACS and AFM Series Annunciators
ACS and AFM Series Annunciators provide visual indications of FACP status in
remote locations. Refer to the appropriate annunciator manual for information on
installation, wiring and operation.
Annunciator addressing is specific to the MS-9200UDLS control panel. The
following table describes the annunciator addresses and the corresponding
addressable devices that will be annunciated at each annunciator address.
The MS-9200UDLS must be programmed for the annunciators installed on the
system. Refer to "Annunciators/UDACT" on page 96 for information on
annunciator programming. Make certain to program the annunciator addresses that
have been physically installed on the system.
Note: The 8 General System Status Points include the following:
Reference
Manual
ACM Annunciator Address Annunciator Displays the Following Points
1 8 General System Status Points & Zones 1 - 56
2 Zones 57 - 99 & 4 NACs
3 SLC Loop, Module Addresses 1 - 64
4 not used
5 SLC Loop, Module Addresses 65 - 99
6 not used
7 not used
8 SLC Loop, Detector Addresses 1 - 64
9 not used
10 SLC Loop, Detector Addresses 65 - 99
11 not used
12 not used
13 not used
14 not used
15 not used
16 not used
17 not used
18 not used
19 not used
20 8 General System Status Points & Zones 1 - 56
21 Zones 57 - 99 & 4 NACs
22 SLC Loop, Module Addresses 1 - 64
23 not used
24 SLC Loop, Module Addresses 65 - 99
25 not used
26 not used
27 SLC Loop, Detector Addresses 1 - 64
28 not used
29 SLC Loop, Detector Addresses 65 - 99
30 not used
31 not used
32 not used
• General Alarm • Alarm Silenced • Battery Fault
• General Trouble • System Off Normal • NAC Fault
• General Supervisory • AC Loss