Installation of Optional Modules Installation
MS-2/MS-4 PN 51512:E 01/18/05 27
2.6.2 4XTMF, 4XLMF and 4XZMF Option Modules
MS-4: The 4XLMF LED Interface Module can only be plugged into connectors J3 and
J5 on the MS-4 main circuit board. The 4XTMF and 4XZMF modules can be plugged
into connectors J3 and J5 or
J4 and J6 on the MS-4 main circuit board. A combination
of any two of the three modules can be installed.
MS-2: Only the 4XTMF module can be plugged into connectors J3 & J5 on the MS-2
main circuit board. (No other option modules can be installed on the MS-2).
The following steps must be followed when installing each of these modules:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP1 (for connectors J3 and J5) and/or JP2 (for connectors J4 and J6)
on the main circuit board to allow the control panel to supervise the placement of
any installed option module
3. Install the two supplied metal standoffs in the locations indicated. These
standoffs provide the required earth ground protection
4. Carefully plug the connectors on the option module into connectors J3 and J5 or
J4 and J6 on the FACP main circuit board, being careful not to bend any pins
5. Secure the option module to the standoff on the main circuit board with the
supplied screws
6. When the installation has been completed, connect the wiring to the modules as
indicated in the following sections
7. Test system for proper operation
ON
12345678
ON
12345678
ON
12345678
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
TROUBLE
TROUBLE
TROUBLE
TROUBLE
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
FIRE ALARM
FIRE ALARM
AC
POWER
NAC
DISABLE
NAC
FAULT
SYSTEM
TROUBLE
POWER
TROUBLE
WALK
TEST
ALARM
SILENCE
ZONE
DISABLE
FIRE ALARM
FIRE ALARM
RESET
WALK
TEST
ALARM
SILENCE
ACK
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE
ENABLE/DISABLE
3
4
2
1
TB1
TB2
TB3
TB5
TB6
TB7
J1
B+ B- B+ B-
NAC 1 NAC 2
+ - + -
Nonreset Reset
B+ B- B+ B-
ZONE 1 ZONE 2
B+ B- B+ B-
ZONE 3 ZONE 4
C TRBL NORM
TROUBLE
C NC NO
ALARM SUPV
C NC NO
J3
J5
J4
J8
J7
J9
TB8
J6
JP1
JP3
SW1
BATTERY
HOT NEUT EARTH
TRANSFORMER 1TRANSFORMER 2
SW2 SW3
JP2
EARTH BATTCHG
CLASS A
CONVERTER
Figure 2.12 4X Option Module Connection to MS-4
J3
J5
J4
J6
JP1 Jumper
Cut to install
module on J3 & J5
JP2 Jumper
Cut to install module on J4 & J6
Standoffs
(when using
J3 & J5
ms4bord.cdr
Standoffs
(when using
J4 & J6