Greenheck Fan OFSD-XXX Ventilation Hood User Manual


 
Part Number 461337
OFSD-XXX, ODFD-XXX,
OFD-XXX, and OSSFD-XXX Series
1½ Hour Combination Fire Smoke or Curtain Fire Dampers
Out of Wall or Out of Floor
Vertical or Horizontal Mount
Installation, Operation, and Maintenance Instructions
OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-
XXX series dampers are intended for installation in
accordance with combination fire smoke dampers
requirements established by:
NFPA National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
BOCA National Building Codes
ICBO Uniform Building Codes
SBCCI Standard Building Codes
New York City (MEA listing # 260-91-M)
California State Fire Marshal
Listing #3225-0981:103 & 3230-0981:104
“UL Classified (see complete marking on product)”
“UL Classified to Canadian safety standards (see
complete marking on product)”
UL Standard 555 & 555S (Classification R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess
of 100°F (38°C).
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will
be repaired or replaced at our option. Greenheck shall
not be liable for damages resulting from misapplication
or misuse of its products. Greenheck will not be
responsible for any installation or removal costs.
Greenheck will not be responsible for any service work
or backcharges without prior written authorization.
Safety Warning:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
Electrical Guidelines
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specifications.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when
the job is complete.
Safety Caution!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring. To avoid causing death
or serious bodily harm to building occupants, follow all
instructions carefully. Dampers must close completely to
preserve the integrity of the fire smoke separation.