SECTION VIII
PROCEDURE FOR FUNCTIONAL CHECK OF
REPLACEMENT COMPONENTS
1. For Models With Johnson Controls DSI (Direct Spark Ignition) Module (G760)
Theory Of Operation;
Start the drying cycle. When the gas burner ignites within the chosen trial for ignition time (6-seconds), the
flame sensor detects gas burner flame and signals the Direct Spark Ignition (DSI) module to keep the gas
valve open...as long as there is a call for heat. The DSI module will LOCKOUT if the gas burner flame
is not sensed at the end of the trial for ignition period. The trial for ignition period will be repeated for a total
of three (3) retries/trials (the initial try and two [2] more retries/trials). If the flame
is not sensed at the end
of the third retry/trial (inter-purge period of 30-seconds) the DSI module will LOCKOUT (L.E.D. [light
emitting diode] flashes).
A steady L.E.D. (light emitting diode) indicator indicates normal operation.
No L.E.D. (light emitting diode) indicator indicates a power or an internal failure has occurred.