24 American Dryer Corp. 113243-1
MANUAL RESET BURNER
HI-LIMIT INSTRUCTIONS
PHASE 7
This dryer was manufactured with a manual reset burner hi-
limit thermostat, which is monitored by the Phase 7 computer.
If the burner hi-limit is open prior to the start of the drying
cycle, the dryer will start momentarily and then shut down,
the Phase 7 computer will display BURNER HIGH LIMIT
FAULT with an audio indication.
If the burner hi-limit opens during a drying cycle, the Phase 7
computer will also display the same error code described
above, along with an audio indication. If the drum temperature
is above 100° F (38° C), the dryer will continue to run with no
heat for 3 minutes or until the drum temperature has dropped
below 100° F (38° C). The clear/stop button on the Phase 7
keyboard (touch pad) must be pressed to clear the error
condition. The open burner hi-limit must be reset manually
prior to the start of the next cycle.
Dual Timer
This dryer was manufactured with a manual reset burner hi-
limit thermostat. If the burner hi-limit is open prior to the start
of the drying cycle, or during the cycle, the dryer will not
recognize the open state of the burner hi-limit and will start
or continue through the drying cycle with no heat. Manual
reset hi-limit must be reset manually.
This hi-temperature condition may be caused due to a
restricted exhaust, poor airflow, or improper burner operation.
The location of the burner hi-limit is on the right side of the
burner box, looking at the burner from the back of the dryer.
WARNING:
Discontinue power to dryer before attempting
to reset hi-limit.
!