For Models with Johnson Direct Spark Ignition (DSI) Controller
(G760)
Theory of Operation:
Start the drying cycle. When the gas burner ignites within the
chosen trial for ignition time (6-seconds), the flame sensor
detects gas burner flame and signals the DSI module to
keep the gas valve open as long as there is a call for heat.
The DSI module will LOCK OUT if the gas burner flame is
not sensed at the end of the trial for ignition period. The trial
for ignition period
will be repeated for a total of three (3) retries/
trials (the initial try and two [2] more retries/trials). If the flame
is not sensed at the end of the third retry/trial (inter-purge
period of 30-seconds) the DSI module will LOCK OUT (light
emitting diode [L.E.D.] diagnostic indicator flashes).
A steady L.E.D. indicator indicates normal operation.
No L.E.D. indicator indicates a power or an internal failure
has occurred.
For Models with Fenwal Controls DSI Module (128937)
Theory of Operation:
Start the drying cycle. When the gas burner ignites within the
chosen trial for ignition time (8-seconds), the flame sensor
detects gas burner flame and signals the DSI module to
keep the gas valve open as long as there is a call for heat.
The DSI module will LOCK OUT if the gas burner flame
is
not sensed at the end of the trial for ignition period. The trial
for ignition period
will be repeated for a total of three (3) retries/
trials (the initial try and two [2] more retries/trials). If the flame
is not sensed at the end of the third retry/trial (inter-purge
period of 30-seconds), the DSI module will LOCK OUT (a
red L.E.D. diagnostic indicator will flash).
An unlit red L.E.D. diagnostic indicator indicates normal
operation.
A lit green L.E.D. diagnostic indicator indicates dryer controller
is calling for heat and that ALL interlocks have been satisfied.