American Dryer Corp. AD-120ES III Clothes Dryer User Manual


 
25
3.
Electrical Connections
NOTE: A wiring diagram is included with each dryer and is affixed to the rear upper right guard/panel
of the dryer.
The only electrical input connections to the dryer are the 3-phase (3ø) power leads (L1, L2, and L3),
GROUND, and in the case of 4-wire service, the neutral. Providing local codes permit, power connections
to the dryer can be made by the use of a flexible underwriters laboratory listed cord/pigtail (wire size must
conform to rating of the dryer), or the dryer can be hard wired directly to the service breaker. In ALL
cases, a strain relief must be used where the wire(s) enter the dryer electrical service (relay) box.
a. Gas Model and Steam Model Dryers
These electrical connections are made at the terminal block located in the electric service/relay box at
the rear, upper left hand corner of the dryer. To gain access into this service box, the service cover
(upper back guard) must be removed.
b. Electric Model Dryers
For electric model dryers made to operate at 208 VAC or 240 VAC, the electrical input connection is
made into the terminal block located at the upper rear of the dryer (refer to the illustration on page
26). For electric model dryers made to operate at 380 VAC, 416 VAC, 440 VAC, or 480 VAC, the
electrical input connection is made to the oven relay located at the upper rear of the dryer (refer to the
illustration on page 26). Input connection wiring must be sized properly to handle the dryer’s current
draw. This information is printed on the dryer’s data label, which is affixed to the left side panel/wall
area behind the control door.
NOTE: A CIRCUIT SERVICING EACH DRYER MUST BE PROVIDED.